DEFROST MENU (continued)
3- ASSIGN OUTPUTS
Press 3 on the Keypad to enter the Assign Outputs
Submenu.
Press ENT to move the cursor to the value to be
changed. Press the CLR key.
Key in the applicable Circuit #. Press ENT.
Electric defrost circuits will typically require two
outputs (one for solenoid and one for heater con-
trol); while offtime and gas defrost circuits require
only one.
Press ESC to return to D
EFROST MENU.